Bacharach's Monoxor® III is a continuous sampling instrument that quickly and accurately measures levels of CO between 0 and 2,000 ppm. In addition, the Monoxor® III is supplied with a stainless steel probe and five feet of tubing to sample CO found in flue gases of residential furnaces, combustion appliances, commercial and industrial boilers.
An optional wireless IrDA printer provides a permanent record of the detected CO level.
Applications
CO safety checks on combustion stack gas and ambient air levels
Analyzing indoor air quality and safety
Furnace and boiler servicing or replacement
Features & Benefits
Quickly measures and displays low levels of CO 0-2,000 ppm
Measures in increments of 1 ppm
Probe and hose assembly for flue gas testing
Highly visible digital display with backlight
Optional IrDA printer for printing test results
Specifications
Range: 0-2,000 ppm
Resolution: 1 ppm
Accuracy: ±5% of reading or 10 ppm, whichever is greater
Operating Temp.:
Instrument: 32-104°F (0-40°C)
Probe: 1,000°F (538°C)
Battery Life: 24 hours continuous (minimum of 16 hours)
Display: Four-digit LCD display w/backlight
Power: 4 'AA' Alkaline Batteries
Printer Port: IrDA or HP protocol
Weight: 16 oz. with batteries
Dimensions: 7.5"H x 3.1"W x 2.1"D (190mm x 79mm x 53mm)
Warranty: 2 years, including sensor