S5 Series Battery Monitoring and Validation System has been designed specifically for your Telecom 48 VDC battery systems.
Our patented and proven impedance measurement technology has the sensitivity required to find failing cells well before they pose a risk.
Plus, with battery sensing harnesses pre-designed and tested for your battery system, installation time is cut in half while increasing system reliability.
Key System Features
BTECH Monitors Key Battery Parameters in Real Time: System Voltage, Float, Charge and Discharge Current, plus ambient and pilot cell temperatures
Impedance measurement spec of 0.1 +/- 0.01 mOhm - the sensitivity required for flooded cells.
Programmable Test & Out-of-Limits Alarms
Battery Discharge Data Logging
Up to 480 Individual Cells and 4 Strings per system
Individual String Current Monitoring for multi-string systems
Complete Isolation from the Battery String
No PC Required
Powered by the +48VDC Charger - No AC Power Required
Facility Management System Integration
MODBUS over TCP/IP for simple third-party software integration
(6) User-configurable Dry Contact Alarms
Alarm and Data Acquisition Options
Local: RS-232 and USB
Remote: 56k Modem and Integral Ethernet
Alarms: Text Message to multiple cell phones, pagers or e-mail addresses, through BVM Software or FMS integration
Safety
BTECH Quick-Disconnect Safety Fuses simplify battery replacements while protecting personnel during installation and maintenance
System Specifications
Measurement Capability: - Total Voltage: 0-600V - Total Number Strings: 4 - Unit Voltage: 1-16 VDC Unit Impedance 100µW to 20mW Temperature - Unit and Ambient: -32°F to 160°F Discharge Events: - Date & Time - System Voltage - Load Current - Power Removed Discharge Logging: Programmable Connection Capacity: - Total Connection Points: 480 - Total Number of Parallel Strings: 4 Measurement Accuracy & Repeatability: - System Voltage: +/ -0.1% Full Scale - Unit Voltage: +/ -0.1% of Reading - Unit Impedance: +/ -0.01 mW - Temperature: +/ -1.0°F |
Power Requirements: -110-250 VAC (UPS Protected Power) Enclosure: - Controller: Metal, Rack or Wall Mount - 24 Unit DCM: Flame Retardant Poly LED Indicators - VM24 DCM: - Green = Power On LED Indicators - SCM600 Controller: - Green = Summary No Alarms - Yellow = Summary Maintenance Alarms - Red = Summary Critical Alarms - Red Equipment = Module not Communicating - Alternating Green = Performing Measurement Software: - BVM 4.1 Windows® based software package designed for Windows® XP and higher CE Mark |