MultiFlame31R-UV/IR火焰检测仪
添加时间:2010-2-9 编辑:C055 阅读:次
- 产品名称:MultiFlame31R-UV/IR火焰检测仪
- 产品定货号:MR-06526-00
The MultiFlame DM-TV6-V is a combined Ultraviolet / infrared flame detector offering exellent flame detection whilst maintaining outstanding false alarm immunity.
Features
The DM-TV6-V is designed to respond to unwanted hydrocarbon fires, whilst maintaining a high degree of false alarm immunity.
The device offers a wide range of output options, as standard and is suitable for use in SIL 2 applications. The unit may be interfaced directly with a wide range of fire panels, controllers and PLC's etc.
The unit is fully configurable using a wireless handheld terminal (TLU) giving true flexibility to the installer. Time delays, sensitivity and output configuration are all set up via the TLU, hazardous area approved handheld unit.
Wireless testing of the optical and output circuits is also possible using the TLU too.
Application
Refineries
Drilling and Production Platforms
Fuel Loading Facilities
Compressor Stations
LNG/LPG Processing and Storage
Gas Turbines
Chemical Plants
Aircraft Hangars
Sports Stadia / Atria
Specification |
General |
Technology |
Ultra Violet / Dual Infra Red |
Fire Types |
Hydrocarbon fires |
Range, n-heptane |
45m (147 feet) 0.3x0.3m (1 sq foot) |
Range, gasoline |
27 m (88 feet) 0.3x0.3 m (1 sq foot) |
Output Signal |
Standard |
4-20mA, max. load impedance 700? (Std.) |
PLC option |
0-22mA (Option for PLC’s) |
Syntel |
Lonworks |
Alarms |
2 x configurable Relays max 1A / 30V |
Electrical |
Power supply |
24V DC, range (18 - 32V DC) |
Power consumption |
70 mA normal; 155 mA during test |
Connection |
0.3 mm2 (22 AWG) - 2.5 mm2 (12 AWG) |
Environmental |
Storage: |
-40°C to +70°C (-40°F to 158°F) |
Operation |
-20°C to +60°C (-4°F to 140°F) |
Humidity |
95% RH (non-condensing) |
Ingress |
IP66 |
RFI/EMI |
Complies with EN50081-1, EN50081-2, |
|
EN50082-1 and EN50082-2. |
Explosion Proof Housing |
Material |
Epoxy coated aluminium (std) |
|
316 L stainless steel (option) |
Approvals |
ATEX |
ATEX II 2 G EEx d II C T6 |
Certificate: |
LCIE03ATEX6263 |
IECEx |
IECEx LCI09.0018 |