ACU2-60-5-2-E2500电流互感器
添加时间:2010-10-14 编辑:X059 阅读:次
- 产品名称:ACU2-60-5-2-E2500电流互感器
- 产品定货号:ME-06574-00
6" Diameter Current Transformer5A base Intelligent Power Meter
Metering of distribution feeders, transformers, generators, capacitor banks and motors
Medium and low voltage systems
Commercial, industrial, utility
Power quality analysis
Web Server and Email Sending
Over Limit Alarm
Remote Switch Controlling
Switch Status Monitoring
UL & CE Certified
The Accuenergy Acuvim II is a high-end multifunction power meter manufactured by Accuenergy. It is the ideal choice for monitoring and controlling of power distribution systems. Some of the features and electric power parameters available on the ultra-compact Acuvim II are: |
True-RMS Measuring Parameter
4-Quadrant Energy
Power Quality Analysis
Over Limit Alarm
Multi Communication Ports (Eg: Ethernet, Modbus)
Web Server and Email Sending
Switch Status Monitoring
Remote Switch Controlling
Module Design (E-Module® Technique) |
Accuenergy Acuvim-2 may be used as a data gathering device for an intelligent Power Distribution System or Plant Automation System. All monitored data is available via a digital RS485 communication port running Modbus™ Protocol. Ethernet and Profibus DP communication are also options and with new wireless technologies and protocols currently under development, the applications for the Accuenergy Acuvim-II meter are limitless. |
|
Specifications |
Parameters |
Accuracy |
Resolution |
Range |
Voltage |
0.2% |
0.1V |
20V ~ 500kV |
Current |
0.2% |
0.001A |
5mA ~ 50000A |
Power |
0.5% |
1W |
-9999MW ~ 9999MW |
Reactive Power |
0.5% |
1 Var |
-9999MVar ~ 9999MVar |
Apparent Power |
0.5% |
1VA |
-9999 ~ 9999MVA |
Power Demand |
0.5% |
1W |
-9999MW ~ 9999MW |
Reactive Power Demand |
0.5% |
1Var |
-9999MVar ~ 9999MVar |
Apparent Power Demand |
0.5% |
1VA |
-9999MVA ~ 9999MVA |
Power Factor |
0.5% |
0.001 |
-1.000 ~ 1.000 |
Frequency |
0.2% |
0.01Hz |
45.00 ~ 65.00Hz |
Energy |
Primary |
0.5% |
0.1kQh |
0 - 99,999,999.9kWh |
Secondary |
0.5% |
0.001kWh |
0 - 99,99.999kWh |
Reactive Energy |
Primary |
0.5% |
0.1kvarh |
0 - 99,999,999.9kVarh |
Secondary |
0.5% |
0.001kvarh |
0 - 999,999.999kVarh |
Apparently Energy |
Primary |
0.5% |
0.1kVAh |
0 - 99,999,999.9kVAh |
Secondary |
0.5% |
0.001kVAh |
0 - 999,999.999kVAh |
Harmonics |
2.0% |
0.1% |
0.0% ~ 100.0% |
Phase Angle |
2.0% |
0.1° |
0.0° ~ 359.9° |
Imbalance Factor |
2.0% |
0.1% |
0.0% ~ 100.0% |
Running Time |
|
0.01h |
0 ~ 9,999,999.99h |