S5 Series Battery Monitoring and Validation System has been designed specifically for your UPS flooded cell battery system.
 
Our patented and proven impedance measurement technology has the sensitivity required to find failing cells well before they pose a risk to your critical systems.
 
Plus, with battery sensing harnesses pre-designed and tested for your battery system, installation time is cut in half while increasing system reliability.
 
Key System Features
BTECH Monitors Key Battery Parameters in Real Time: System Voltage, Float, Charge and Discharge Current, plus ambient and pilot cell temperatures
Programmed Cell Impedance Measurement: Up to 24x / Day
Programmable Test & Out-of-Limits Alarms
Battery Discharge Data Logging
Up to 480 Individual Cells and 4 Strings per system
Individual String Current Monitoring for multi-string systems
Complete Isolation from the Battery String
No PC Required
Facility Management System Integration
MODBUS over TCP/IP for simple third-party software integration
(6) User-configurable Dry Contact Alarms
Alarm and Data Acquisition Options
Local: RS-232 and USB
Remote: 56k Modem and Integral Ethernet
Alarms: Text Message to multiple cell phones, pagers or e-mail
addresses, through BVM Software or FMS integration
 
Safety
BTECH Quick-Disconnect Safety Fuses simplify battery replacements while protecting personnel during installation and maintenance
System Specifications
Measurement Capability:
- Total Voltage: 0-600V
- Total Number Strings: 4
- Unit Voltage: 1-16 VDC
Unit Impedance 100µW to 20mW
Temperature - Unit and Ambient: -32°F to 160°F
Discharge Events:
- Date & Time
- System Voltage
- Load Current
- Power Removed
Discharge Logging: Programmable
Connection Capacity:
- Total Connection Points: 480
- Total Number of Parallel Strings: 4
Measurement Accuracy & Repeatability:
- System Voltage: +/ -0.1% Full Scale
- Unit Voltage: +/ -0.1% of Reading
- Unit Impedance: +/ -0.01 mW
- Temperature: +/ -1.0°F
Power Requirements:
-110-250 VAC (UPS Protected Power)
Enclosure:
- Controller: Metal, Rack or Wall Mount
- 24 Unit DCM: Flame Retardant Poly
LED Indicators - VM24 DCM:
- Green = Power On
LED Indicators - SCM600 Controller:
- Green = Summary No Alarms
- Yellow = Summary Maintenance Alarms
- Red = Summary Critical Alarms
- Red Equipment = Module not Communicating
- Alternating Green = Performing Measurement
Software:
- BVM 4.1 Windows® based software package designed for Windows® XP and higher
CE Mark
 